(MOUNTING CLIPS INSTALLED)
5.51
(139.9)
7.70 (195.5) 2.00 (50.8)
5.7
(146)
7.9 (202)
2.97 (76)
Module sold
separately
GRAPHITE™ SERIES
7" Color Touchscreen Operator Interface
Installation Guide
DIMENSIONS In inches (mm)
See the Red Lion website at www.redlion.net or the enclosed
USB thumbdrive for full user manual, Crimson software and
software manual.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired. Do not use this unit to directly
command motors, valves, or other actuators not equipped with safeguards. To
do so can be potentially harmful to persons or equipment in the event of a fault
to the unit.
ORDERING INFORMATION
DESCRIPTION PART NUMBER
7" color touch screen, indoor use, 24 VDC powered G07C0000
7" color touch screen, indoor/outdoor use, 24 VDC powered G07S0000
SPECIFICATIONS
POWER: +24 VDC ±20%
G07C G07S
Typical Power HMI only: 9 W 10 W
Maximum Power HMI only: 16 W 17 W
HMI With Module(s): 37 W 38 W
Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited
Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit
according to IEC 61010-1.
Power connection via removable three position terminal block.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to 60 °C
Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Listed: File #E302106
Type 4X Indoor / IP66 Enclosure rating (Face only) for all models
Type 4X Outdoor Enclosure rating (Face only) for G07Sxxxx models
CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)
CONSTRUCTION: Cast aluminum enclosure with NEMA 4X/IP66 rating for
indoor/outdoor use when correctly fitted with the gasket provided. Installation
Category II, Pollution Degree 2.
WEIGHT: 2.26 lb. (1.03 Kg)
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
Drawing No. LP0907B
Released 04/14
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
C
US LISTED
U
L
R
IND. CONT. EQ.
34AD

Other manuals for red lion GRAPHITE SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the red lion GRAPHITE SERIES and is the answer not in the manual?

red lion GRAPHITE SERIES Specifications

General IconGeneral
Brandred lion
ModelGRAPHITE SERIES
CategoryControl Unit
LanguageEnglish

Related product manuals