15
ELECTRICAL DATA—RRKA- SERIES
Unit Operating
Voltage Range
Model No.
RRKA-
Minimum Circuit
Ampacity
Minimum Overcurrent
Protection Device Size
Maximum Overcurrent
Protection Device Size
No. Volts Phase HP
Amps
(FLA)
Amps
(LRA)
Unit Information Evaporator Fan
A036CK04E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A036CK06E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A036CK08E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A036CK10E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A042CK04E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A042CK06E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A042CK08E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A042CK10E 187-253 20/20 25/25 30/30 1 208/230 1 1/2 2.4 4.8
A048CK06E 187-253 25/25 30/30 35/35 1 208/230 1 3/4 4.4 9.6
A048CK08E 187-253 25/25 30/30 35/35 1 208/230 1 3/4 4.4 9.6
A048CK10E 187-253 25/25 30/30 35/35 1 208/230 1 3/4 4.4 9.6
A060CK10E 187-253 30/30 35/35 45/45 1 208/230 1 3/4 4.4 9.6
Model No.
RRKA-
Compressor Motor Condenser Motor
No. Volts Phase
HP
2
RPM
Amps
1
(RLA)
Amps
1
(LRA)
No. Volts Phase
HP
2
Amps
1
(FLA)
Amps
1
(LRA)
A036CK04E 1 208/230 3 3 1/3 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A036CK06E 1 208/230 3 3 1/3 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A036CK08E 1 208/230 3 3 1/3 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A036CK10E 1 208/230 3 3 1/3 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A042CK04E 1 208/230 3 3 1/2 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A042CK06E 1 208/230 3 3 1/2 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A042CK08E 1 208/230 3 3 1/2 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A042CK10E 1 208/230 3 3 1/2 3450 12.5/12.5 88/88 1 208/230 1 1/5 1.3 2.3
A048CK06E 1 208/230 3 4 3450 14.7/14.7 115/115 1 208/230 1 1/3 1.7 4.7
A048CK08E 1 208/230 3 4 3450 14.7/14.7 115/115 1 208/230 1 1/3 1.7 4.7
A048CK10E 1 208/230 3 4 3450 14.7/14.7 115/115 1 208/230 1 1/3 1.7 4.7
A060CK10E 1 208/230 3 5 3450 18.6/18.6 128/128 1 208/230 1 1/3 1.7 4.7
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.