EasyManuals Logo

Sanyo C1872 User Manual

Sanyo C1872
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
NOTE
Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)
(1) Low pressure performance chart
(2) Operating current performance chart
(3) Indoor discharge air performance chart
Indoor Unit XS1872 & PNR-XS1872 Outdoor Unit C1872 or CL1872
Hi FanLo Fan
Low pressure at wide tube service valve
psig(MPaG)
Operating current (A)
73
(0.5)
102
(0.7)
131
(0.9)
Outdoor inlet air D.B. temp. °F(°C)
Outdoor inlet air D.B. temp. °F(°C)
Indoor discharge air temperature °F(°C)
77
(25)
86
(30)
95
(35)
104
(40)
Hi FanLo Fan
5
6
7
8
9
10
77
(25)
86
(30)
95
(35)
104
(40)
Outdoor inlet air D.B. temp. °F(°C)
Indoor Air Temp.86
°
F (30
°
C)
80
°
F (27
°
C)
75
°
F (
24
°
C)
Indoor Air Temp.86°F (30°C
)
80°F (27°C)
75
°F (
24
°C)
Indoor Air Temp.86
°
F (30
°
C)
80
°
F (27
°
C)
75
°
F (
24
°
C)
Indoor Air Temp.86°F (30°C)
80°F (27°C)
75
°F (
24
°C)
Hi FanLo Fan
32
(0)
41
(5)
50
(10)
59
(15)
68
(20)
77
(25)
86
(30)
95
(35)
104
(40)
Indoor Air Temp.86
°
F (30
°
C)
75
°
F (
24
°
C)
Indoor Air Temp.86°F (30°C)
75
°F (
24
°C)
80
°
F (27
°
C)
80°F (27°C)
31

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo C1872 and is the answer not in the manual?

Sanyo C1872 Specifications

General IconGeneral
BrandSanyo
ModelC1872
CategoryAir Conditioner
LanguageEnglish

Related product manuals