EasyManuals Logo

Sanyo CM2472 User Manual

Sanyo CM2472
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
5
G Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for tele-
vision, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.
G install in a sturdy manner to avoid increased operating
noise.
Table 3
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
Max. Max. Allowable Total Limit of Limit of Elevation Required Amount
Allowable Tubing Length Total Tubing Length Difference of Additional
Model Tubing Length at shipment (L1+L2+L3) or (H1, H2, H3, H4) Refrigerant
per unit (L1+L2+L3) or (L1+L2+L3+L4) (ft.) (oz./ft.)*
(ft.) (L1+L2+L3+L4) (ft.)
(ft.)
CM1972/CLM1972 82 150 (L1+L2+L3) 150 (L1+L2+L3) 50
CM2472/CLM2472 82 150 (L1+L2+L3+L4) 200 (L1+L2+L3+L4) 50 0.22
CM3172/CLM3172 100 150 (L1+L2+L3+L4) 230 (L1+L2+L3+L4) 50 0.22
07-156 CM-CLM1972-3172 6/6/07 9:35 AM Page 5

Other manuals for Sanyo CM2472

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo CM2472 and is the answer not in the manual?

Sanyo CM2472 Specifications

General IconGeneral
BrandSanyo
ModelCM2472
CategoryAir Conditioner
LanguageEnglish

Related product manuals