AY/AE-A079E
AY/AE-A099E
10
Figure Y-6
2-4 Fan only operation
The indoor fan motor always turns on.
3. Fan speed
Fan speeds are given by the indoor fan motor, "H",
“M”, “L”, “UL” and "D" which are available in the
following operation mode.
Table Y-2
FAN Switch HEAT COOL FAN ONLY
HIGH H M M
LOW M L L
SOFT L UL UL
2-3 Heat operation
The compressor turns on or off, at State 2 , turns
on continuously at State 1 & 3 .
Figure Y-5
Table Y-1
Compressor Fan Speed
Cooling zone ON “UL”
Dehumidifying ON “D”
zone
Circulating OFF “D” or OFF
zone
2-2 DRY operation
On the switch on, the compressor always starts
to operate for 2 minutes with fan speed “D”
(slower than “UL”).
The microcomputer reads the room temperature
2 minutes after this first compressor operation.
This room temperature is set as the preset
temperature automatically.
The preset temperature ranges from 18˚C to
32˚C. When the room temperature is below 18˚C,
the preset temperature is set to 18˚C, and when
the room temperature is over 32˚C, the preset
temperature is set to 32˚C.
Dry operation is divided into three zones (Cooling
zone, Dehumidifying zone and Circulating zone)
by thermostat lines (D1 to D3), and the
compressor and the fan motor are controlled in
each zone as shown in Table Y-1.