EasyManuals Logo
Home>Siemens>Switch>8DJH

Siemens 8DJH Operator's Guide

Siemens 8DJH
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
SIEMENS 8DJH Ring Main Operator Guide Circuit Breaker Panel
1
L
(Type 2)
CLOSE
OPEN
2756
b
a
CLOSE
OPEN
2756
CLOSE
OPEN
2756
WARNING
Check that the Ready For Service (gas) Gauge indicates GREEN before operation
DO NOT OPERATE switchgear if the pointer is in the RED region
1
Slide the Isolator/Earth Switch Control Gate down to
open the Earth Shutter. 2
Insert the Operating Lever and rotate anti- clockwise
to open the Earth Switch. 3
Remove the Operating Lever. Check the
Control Gate has returned to the mid position.
A
Feeder Earthed u
Feeder Isolated u
1
Slide the right-hand Control Gate up to open the
Isolator Shutter.
4
(a) Remove the Operating Lever. Check the
Control Gate has returned to the mid position.
(b) Slide the left-hand Control Gate up to open the
Circuit Breaker Spring Charge Shutter.
2
Insert the Operating Lever and rotate clockwise
to close the Isolator Switch.
5
Insert the Operating Lever and rotate clockwise to
charge the Circuit Breaker Spring. It will click and hold
when rotated enough (70°).
Note: The aperture is sprung to eject the handle automatically.
It must be pushed in firmly and held to rotate.
3
For panels where the Circuit Breaker Spring Charge
mechanism is motorised, the spring is automatically
recharged immediately after the Circuit Breaker is
opened. In this case, steps 4 and 5 can be omitted.
6
Remove the Operating Lever. Press the CLOSE
button VERY HARD.
B
Feeder Isolated u
Feeder Connected u
These instructions detail mechanical operation of standard designs only

Other manuals for Siemens 8DJH

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 8DJH and is the answer not in the manual?

Siemens 8DJH Specifications

General IconGeneral
BrandSiemens
Model8DJH
CategorySwitch
LanguageEnglish

Related product manuals