PXL Conventional Fire Alarm Control Panel
Operation
38
Responding to a Supervisory Condition
HOW THE SYSTEM ANNUNCIATES SUPERVISORIES
When a supervisory alarm is detected, the system causes the
SUPERVISORY LED and one of the zone LEDs to flash and the
systems internal audible to sound.
TO ACKNOWLEDGE SUPERVISORIES
1. Unlock and open the door.
2. Press the ACKNOWLEDGE button to acknowledge the
supervisory condition. The system SUPERVISORY LED and the
zone LEDs on the front panel stop flashing and remain on and
the systems internal audible silences.
TO RESET
The system operator should RESET the system by pressing the
RESET button. (The system will not reset until all alarms,
supervisories, and troubles are acknowledged and all conditions are
returned to normal.)
Responding to a Trouble Condition
HOW THE SYSTEM ANNUNCIATES TROUBLES
When a trouble is detected, the system causes the TROUBLE LED
and the appropriate Zone TROUBLE LEDs on the front panel to
flash and the systems internal audible to sound.
TO ACKNOWLEDGE TROUBLES
1. Unlock and open the door.
2. Press the ACKNOWLEDGE button to acknowledge the troubles.
The system TROUBLE and the individual zone TROUBLE LEDs
on the front panel stop flashing and remain on. The systems
internal audible silences.
NOTE: Acknowledged troubles will be reported again in 24
hours if they are not cleared.
TO RESET
The system operator should RESET the system by pressing the
RESET button. (The system will not reset until all alarms,
supervisories, and troubles are acknowledged and all conditions are
returned to normal.)
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CERBERUS PYROTRONICS PXL and is the answer not in the manual?

Siemens CERBERUS PYROTRONICS PXL Specifications

General IconGeneral
BrandSiemens
ModelCERBERUS PYROTRONICS PXL
CategoryControl Panel
LanguageEnglish

Related product manuals