IntroductionPXL Conventional Fire Alarm Control Panel
1
1 The PXL Control Panel
INTRODUCTION
The CERBERUS PYROTRONICS
TM
PXL Control Panel is a micro-
processor-based conventional fire protection system. The basic PXL
System has 12 Initiating Device Circuits (IDCs), 4 Notification Appli-
ance Circuits (NACs), and 3 dedicated Form C relays for Alarm,
Trouble, and Supervisory conditions.
Components of the Basic PXL System
The following components are included in the basic PXL Control
Panel:
PCM-1 Main Control Board with
- 12 Initiating Device Circuits
- user controls
PPS-10M Power Supply with
- 4 Notification Appliance Circuits
- 3 dedicated Form C relays
PTX-12 Power Transformer
PSE-1 Enclosure with
- PMK-1 Mounting Bracket
Batteries, which must be purchased separately, that are capable
of supplying all power necessary to operate the PXL and supply
1 amp auxiliary +24 VDC and up to 10 amps of NAC current at
24 volts when in alarm.
NOTE: Both the Auxiliary current and the NAC current together
cannot exceed 10 Amps.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CERBERUS PYROTRONICS PXL and is the answer not in the manual?

Siemens CERBERUS PYROTRONICS PXL Specifications

General IconGeneral
BrandSiemens
ModelCERBERUS PYROTRONICS PXL
CategoryControl Panel
LanguageEnglish

Related product manuals