5/18
Building Technologies CC1N7130en
15.03.2018
Life cycle
Burner controls has a designed lifetime* of 250,000 burner startup cycles which, under
normal operating conditions in heating mode, correspond to approx. 10 years of usage
(starting from the production date given on the type field).
This lifetime is based on the endurance tests in the standard EN 298.
A summary of the conditions has been published by the European Control
Manufacturers Association (Afecor) (www.afecor.org).
The designed lifetime is based on use of the burner controls according to the
manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number
of burner startup cycles, or the respective time of usage, the burner control is to be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
Mechanical design
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.
It is of plug-in design and engages audibly in the base. Burner controls LMO are
designed in black plastic.
The housing accommodates the
microcontroller for the control sequence and the print relays for load control
electronic flame signal amplifier
lockout reset button with its integrated multicolor signal lamp (LED) for operational
status and fault status messages and the socket for connecting the OCI400
interface or the AGK20 lockout reset button extension
Multicolor indication of operational status and fault status messages
Transmission of operational status and fault status messages and detailed service
information via additional OCI400 interface and ACS410 PC software
Indication and
diagnostics
Service notes
The service adapters can only be used for a short time. They may only be used in
supervised operation by qualified staff.

Other manuals for Siemens LMO14 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMO14 Series and is the answer not in the manual?

Siemens LMO14 Series Specifications

General IconGeneral
BrandSiemens
ModelLMO14 Series
CategoryControl Unit
LanguageEnglish

Related product manuals