Setting the programmable timers
The
RDG100T / RDG160T / RDG160TU provides
8 programmable timers A1…A8 each of which can be
assigned to one or several days. To set an auto timer, proceed as follows:
1.
Press the program mode button twice to select auto timer setting .
2.
Turn the rotary knob to the desired timer A1…A8 that you wish to set and press button (OK).
3.
Turn the rotary knob to set the Comfort mode start time and confirm by pressing button
(OK).
4.
Turn the rotary knob to set the Comfort end time
or Economy start time and confirm by
pressing button (OK).
5.
Weekday , and blink. Press button (OK) to select or
(Esc) to deselect each day and
advance to the next day.
6.
After the 7th day is set, all selected weekdays blink. Confirm setting for actual timer by pressing
button (OK) and advance to the ne
xt timer. To set the next timer, repeat steps 3 through 6, or
press (Esc) to leave the setting mode.
Notes:
- To save your settings, remember to press OK in step 6 above before pressing Esc to leave the setting mode.
- The timer function can be disabled by setting P02 = 3 or P02 = 4 (RDG160T / RDG160TU only)
Viewing the settings
1.
Press the program mode button twice to select auto timer setting .
2.
Turn the rotary knob to review the 8 auto timers.
3.
Press button (Esc) to return to normal operation.
Temporary timer for extended presence or absence
The
Comfort and Economy modes can be temporarily extended from 0.5 to 9.5 hours using
the
temporary timer.
1.
To set the temporary timer, press and hold the operating mode button for maximum 3 seconds.
While holding the button, turn the rotary knob clockwise or counterclockwise as required.
a) Turn the rotary knob clockwise to extend Comfort mode.
Display:
0....+9:30
b) Turn the rotary knob counterclockwise to extend Economy mode.
Display: 0....-9:30
After the temporary timer has e
lapsed, the thermostat will resume operation in Auto Timer mode.
Reloading the default timer settings
1.
Press the program mode button twice to select auto timer setting .
2
. Press button (OK) to enter the timer setting mode.
3.
Press the program mode button for at least 3 seconds; then “rESis displayed.
4.
Press button (OK) to confirm reloading the default timer settings, or
(Esc) to leave without
change.
Default
settings
Weekdays
Time of day when thermostat is in Comfort mode
Mon (1)Fri (5)
06:30 08:30 (A1)
17:30 22:30 (A2)
Sat (6)
08:0023:00 (A3)
Sun (7)
08:0022:30 (A4)
For the remaining time, the thermostat is in Economy mode.
Timers A5 - A8 are free with no default settings.
Button lock
To lock or unlock the buttons manually,
press and hold the fan mode button for 3
seconds. The buttons are locked or unlocked in this manner if P14 is set to 2
If P14 is set to 1, the thermostat automatically locks the button 10 seconds
after the
last adjustment
Control parameters
If you want to change control parameters, proceed as follows:
1.
Press left and right buttons simultaneously for at least 4 seconds.
2.
Release them and, within 2 seconds, press the right button again until “P01” is displayed.
3.
Select the required parameter by turning the rotary knob.
4.
Press button (OK). The current value of the selected parameter starts blinking and
can be changed
by turning the rotary knob.
5.
Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.
If you wish to adjust additional parameters, repeat ste
ps 3 through 5, or press
(Esc) to leave the
parameter setting mode.
No.
Parameter name
Default value*
Setting range*
Adj.
P01
Control sequence
2-pipe / 2-stage: 1
4-pipe: 4
0 = heating only
1 = cooling only
2 = H/C changeover, manually
3 = H/C changeover, auto
4 = heating and cooling
P02 Mode selection via operating
mode button
1 1 = Auto / Comfort /
Protection mode
2 = Auto / Comfort / Economy /
Protection mode
3 = Comfort / Protection mode
4 = Comfort / Economy /
Protection mode
P03 Mode selection via fan mode
button
0 0 = Auto / Manually
1 = Manually
2 = Auto / Manually / Protection
mode
P04 Selection of °C or °F RDG100T/160T: 0
RDG160TU: depends on
wizard setting
0 = °C
1 = °F
P05 Sensor calibration 0.0 K
(0.0 °F)
3...3 K
(–6...6 °F)
P06 Standard temperature display 0 0 = Room temperature
1 = Setpoint
P08 Comfort basic setpoint 21 °C
(70 °F)
5...40 °C
(41 °F…104 °F)
P09 Minimum setpoint limitation
in Comfort mode
5 °C
(41 °F)
5 ... 40 °C
(41…104 °F)
P10 Maximum setpoint limitation
in Comfort mode
35 °C
(95 °F)
5...40 °C
(41 °F…104 °F)
P11
Setpoint for heating in
Economy mode (WheatEco)
15 °C
(59 °F)
OFF, 5 °C…WcoolEco
(OFF, 41 °F …WcoolEconomy)
P12
Setpoint for cooling in
Economy mode (WcoolEco)
30 °C
(86 °F)
OFF, WheatEco…40 °C
(OFF, WheatEconomy…104 °F)
P13
Electric heater in cooling
mode
ON
OFF = Disabled
ON = Enabled
P14
Button lock
0
0 = Disabled
1 = Automatically
2 = Manually
P15
Fan speed in dead zone
(Comfort mode)
0
0 = Disabled
1 = Stage 1 (H or C)
2 = Stage 1 (Cooling only)
* Degree Fahrenheit parameter selections are only applicable to RDG160TU version
The control parameters displayed depend on the DIP switch settings made
Siemens Switzerland Ltd
Subject to change
B3181.5en
2014-08-13

Other manuals for Siemens RDG100T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDG100T and is the answer not in the manual?

Siemens RDG100T Specifications

General IconGeneral
BrandSiemens
ModelRDG100T
CategoryThermostat
LanguageEnglish

Related product manuals