CE1B3070en / 01.03.2010 Subject to alteration Siemens Building Technologies / HVAC Products
NOTE:
You can press the OVERRIDE button on the receiver to manually switch ON/OFF for a faulty
room unit or transmission protocol.
NOTE:
You must re-execute the workflow for commissioning the set to reestablish a connection between
the room controller and receiver .
Front View Receiver
LED Signal Indicator LED Relay Indicator
Orange LED indicates relay is on.
The signal is good when the
LED flashes green.
A flashing red LED indicates
that there is no signal.
OVERRIDE Button
Press this button to overwrite transmitter
values.
RESET: Press the LEARN & OVERRIDE
button for 4 seconds to delete all transmitter
addresses.
LEARN Button
Rear View Room Unit
(Transmitter)
Press the button to learn a transmitter
address.
Learn Button
TEST Button
Release learn telegram Used for testing transmission.
Front View Receiver
Configuration instructions for the Siemens RDH10RF/SET
The Transmitter RDH10RF and the receiver RCR10/433 are set to communicate (bonded) with each
other at the factory. If they fail it is necessary to re bond the units due to loss of communication please
follow the following instructions.
1. Reset receiver by simultaneously pressing the LEARN & OVERRIDE button for 4 seconds.
2. Press and release the LEARN button. This set the receiver to learn mode.
3. Press and release the LEARN button on the back of the transmitter.
4. A green flashing or solid LED indicates a good signal, a red flashing or solid LED indicates no
signal.
5. To test transmission, press the TEST button on the transmitter, switches the relay on in
the receiver regardless of temperature. The RF TEST symbol appears on the thermostat display.
6. An orange LED indicates that the relay is on.