Parameter data records
B.7 Parameter data records of the high-speed counters
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
162 Manual, 09/2016, A5E35306440-AB
B.7
Parameter data records of the high-speed counters
You can change the parameters of the High Speed Counter in RUN mode. The WRREC
instruction is used to transfer the parameters to the High Speed Counter using data
record 128.
If errors occur when transferring or validating parameters with the WRREC instruction, the
High Speed Counter continues operation with the previous parameter assignment. The
STATUS output parameter then contains a corresponding error code. If no error has
occurred, the length of the data actually transferred is entered in the STATUS output
parameter.
You will find a description of the "WRREC" instruction and the error codes in the STEP 7
(TIA Portal) online help.
Data record structure
The following table shows you the structure of data record 128 with the counter channel. The
values in byte 0 to byte 3 are fixed and must not be changed. The value in byte 4 may only
be changed by parameter reassignment and not in RUN mode.
Table B- 11 Parameter data record 128 - HSC parameter header
Bit
7
6
5
4
3
2
1
0
Byte
0
Major Version = 1
Minor Version = 0
1
Length of parameter data of the channel = 48
2
Reserved = 0
1)
3
1)
Reserved bits must be set to 0
Table B- 12 Parameter data record 128 - operating mode
Bit →
7
6
5
4
3
2
1
0
Byte
Operating mode
4
Reserved = 0
1)
Operating mode:
0000
B
: Deactivated
0001
B
: Counting
0010
B
: Measuring
0011 to 1111
B
: Reserved
1)
Reserved bits must be set to 0

Table of Contents

Other manuals for Siemens Simatic S7-1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-1500 and is the answer not in the manual?

Siemens Simatic S7-1500 Specifications

General IconGeneral
Protection ClassIP20
Programming LanguageLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
MemoryWork memory and load memory (integrated or external memory card)
I/O ModulesDigital I/O, Analog I/O, Technology modules, Communication modules
Safety IntegratedYes (with fail-safe CPUs and modules)
RedundancyCPU redundancy possible with specific CPU types
Temperature Range0°C to 60°C (horizontal installation)
Digital InputsScalable through digital input modules
Digital OutputsScalable through digital output modules
Analog InputsScalable through analog input modules
Analog OutputsScalable through analog output modules
BackplaneIntegrated backplane for module connection
Real-time clockIntegrated real-time clock
CPU TypeVarious models available (e.g., CPU 1511-1 PN, CPU 1513-1 PN, CPU 1515-2 PN, CPU 1517-3 PN, CPU 1518-4 PN/DP)

Related product manuals