I
I
J
H
J
B
B
C
C
A
A
1
2
SINAMICS G120 Input Choke Installation Instructions
Ground
Frame Size A B C
Tightening Torque (Nm)
1.1 1.5 2.25
Tightening Torque (lbf.in)
10 13.3 20
Recommended Minimum
Cable Cross Section (mm
2
)
1 1.5 2.5
Maximum Cable Cross
Section (mm
2
)
2.5 6 10
Recommended Minimum
Cable Cross Section (AWG)
18 AWG 16 AWG 14 AWG
Maximum Cable Cross
Section (AWG)
14 AWG 10 AWG 8 AWG
Wire Size and Terminal Torques - Field Wiring Connectors
1
2
D
E
F
H
G
A B C D E F G H I J
6SE6400-3CC00-2AD3 FSA 200 - 480 1.9 3 200 75.5 49.5 200 75.5 216.4 - 160 56 187 M4 (2) 1.31
6SE6400-3CC00-4AD3 FSA 200 - 480 3.5 3 200 75.5 49.5 200 75.5 216.4 - 160 56 187 M4 (2) 1.35
6SE6400-3CC00-6AD3 FSA 200 - 480 4.8 3 200 75.5 49.5 200 75.5 216.4 - 160 56 187 M4 (2) 1.41
6SL3203-0CD21-0AA0 FSB 200 - 480 9 3 270 153 70 270 153 235.25 133 258 133 258 M4 (4) 3.4
6SL3203-0CD21-4AA0 FSB 200 - 480 12.1 3 270 153 70 270 153 235.25 133 258 133 258 M4 (4) 3.4
6SL3203-0CD2
2-2AA0 FSC 200 - 480 20.5 3 336 189 50 336 189 235 167 323 167 323 M5 (4) 5.82
6SL3203-0CD23-5AA0 FSC 200 - 480 29.3 3 336 189 50 336 189 235 167 323 167 323 M5 (4) 5.82
Fixing Siz
e