SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
59
Fault rectification
5
5.1
List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 5- 1 The most important alarms and faults of the safety functions
Number
Cause
Remedy
F01600
STOP A Triggered
STO Select and then deselect again.
F01650 Acceptance test required Carry out acceptance test and create test certificate.
Switch the Control Unit off and then on again.
F01659 Write task for parameter rejected Cause: The converter should be reset to the factory setting. The resetting of
the safety functions is, however, not allowed, because the safety functions
are currently enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = …
Enter password for the safety functions.
p0970 = 5 Reset Start Safety Parameter.
The converter sets p0970 = 5 if it has reset the parameters.
Then reset the converter to the factory setting again.
A01666 Static 1 signal atF-DI for safe
acknowledgment
F-DI to a logical 0 signal.
A01698 Commissioning mode active for
safety functions
This message is withdrawn after the Safety commissioning has ended.
A01699 Shutdown path test required After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
F30600
STOP A Triggered
STO Select and then deselect again.
Table 5- 2 The most important alarms and faults
Number
Cause
Remedy
F01018 Power-up aborted more than
once
1. Switch off the converter power supply and switch it on again.
2. After this fault, the converter powers up with the factory settings.
3. Recommission the converter.
A01028 Configuration error Explanation: Parameterization on the memory card has been created with a
different type of module (order number, MLFB)
Check the module parameters and recommission if necessary.
F01033 Unit switchover: Reference
parameter value invalid
Set the value of the reference parameter to a value other than 0.0 (p0304,
p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating