List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 5- 1 The most important alarms and faults of the safety functions
STO Select and then deselect again.
F01650 Acceptance test required Carry out acceptance test and create test certificate.
Switch the Control Unit off and then on again.
F01659 Write task for parameter rejected Cause: The converter should be reset to the factory setting. The resetting of
the safety functions is, however, not allowed, because the safety functions
are currently enabled.
Remedy with operator panel:
Enter password for the safety functions.
p0970 = 5 Reset Start Safety Parameter.
The converter sets p0970 = 5 if it has reset the parameters.
Then reset the converter to the factory setting again.
A01666 Static 1 signal atF-DI for safe
F-DI to a logical 0 signal.
A01698 Commissioning mode active for
This message is withdrawn after the Safety commissioning has ended.
A01699 Shutdown path test required After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
STO Select and then deselect again.
Table 5- 2 The most important alarms and faults
F01018 Power-up aborted more than
once
1. Switch off the converter power supply and switch it on again.
2. After this fault, the converter powers up with the factory settings.
3. Recommission the converter.
A01028 Configuration error Explanation: Parameterization on the memory card has been created with a
different type of module (order number, MLFB)
Check the module parameters and recommission if necessary.
F01033 Unit switchover: Reference
Set the value of the reference parameter to a value other than 0.0 (p0304,
p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).