I
-Drill holes with φ10 drill. Depth: at least 60mm.
-Mark position of four holes.
-Tighten the expansion tubes. Screw the expansion screws.
-Match the inverter with the bracket.
375.0mm
263.0mm
-Overview of Mounting
- Screw the set screw on the left-bottom
of inverter tightly.
- If necessary, costomer can install an
anti-theft lock on the left-bottom of the
inverter.
-Align the halves connectors
10 mm
10 mm
PVconnectionsteps(PV cable size:12AWG):
3.Insert AC cable into AC port
through screw cap.
a.L-wire,N-wire connection
b.PE wire connection
4. Connect the wire to the AC terminal in the inverter.
AC connectionsteps(AC cable size:refer to table1&table2):
1.Remove thetop-down cover.
2. Make AC wires.
60mm
12mm
PV and AC Connection
E Version inverter:EPSfunctioncanbeachieved manually or automatically.
EPS wiring diagram EPS connection steps:
Note: ConnectPEwire into
N port at right !
1. Make wires(EPS cable size: refer to the table below)
2. Insert EPS cable into EPS port through screw cap.
L N N
L N N
Note: The black cable( the N
port at right side) has
been wired during the
manufactory.
60mm
12mm
EPS Connection(for I version and E version )
+
-
Communication interface bewteen inverter and battery is Rs485 orCAN with aRJ45
connector.
Note:
The battery communication can only work when the battery BMS iscompatible
withtheinverter.
A:Power Connection Steps:
current of
breaker>32A
Press down spring until it clicks audibly into place
The ne wire strands must be seen in the champer
wire strands
Battery Connection
Before connecting to battey, please install a nonpolarized DC breaker to make
sure inverter can be securely disconnected during maintanance.
Battery breaker
Voltage
Current[A]
32A
Model
X1-Hybrid-3.0-D
X1-Hybrid-3.0-N
X1-Hybrid-3.7-D
X1-Hybrid-3.7-N
X1-Hybrid-4.6-D
X1-Hybrid-4.6-N
X1-Hybrid-5.0-D
X1-Hybrid-5.0-N
Nominal voltage of DC breaker should be larger than maximum
voltage of battery.
Mounting Steps
Cable
4-5mm²
Micro-breaker
4-5mm² 5-6mm² 5-6mm²
20A 20A 32A 32A
Model
X1-Hybrid-3.0-D
X1-Hybrid-3.0-N
X1-Hybrid-3.7-D
X1-Hybrid-3.7-N
X1-Hybrid-4.6-D
X1-Hybrid-4.6-N
X1-Hybrid-5.0-D
X1-Hybrid-5.0-N
Model
X1-Hybrid-3.0-D
X1-Hybrid-3.0-N
X1-Hybrid-3.7-D
X1-Hybrid-3.7-N
X1-Hybrid-4.6-D
X1-Hybrid-4.6-N
X1-Hybrid-5.0-D
X1-Hybrid-5.0-N
Cable
8-10mm²
Micro-breaker
8-10mm²
10-13mm²
10-13mm²
50A
50A
63A 63A
table1. E Version & C Version
table2. I Version
4 6AWG AC terminals and 4 10AWG AC terminals for Version I
4 10AWG AC terminals and 4 8AWG AC terminals for Version E and Version C
AC terminal x8 *:
Inverter x1
Bracket x1
Expansion tubes x4
Expansion screws x4
DC connectors
(positive x2, negative x2)
Battery connectors
(positive x1, negative x1)
DC pin connectors
(positive x2, negative x2)
Version I
Version E&C
AC terminal x8 *
Grounding nut x1
Set screw(for mounting) x1
Quick installation guide x1
Warranty card x1
User manual x1
Ring terminal (external) x1
Ring terminal (internal) x1
Gasket x1
Meter x1
Wifi module(optional) x1
Smart Plug(optional) x1
EPS Cable
5mm²
EPS breaker
5mm² 5mm² 5mm²
25A 25A 32A 32A
Model
X1-Hybrid-3.0-D
X1-Hybrid-3.0-N
X1-Hybrid-3.7-D
X1-Hybrid-3.7-N
X1-Hybrid-4.6-D
X1-Hybrid-4.6-N
X1-Hybrid-5.0-D
X1-Hybrid-5.0-N
table. Cable and Micro-breaker recommended
BMS_CANH
GNDX X
BMS_CANL
Definition
2
3 4
5
6 7 81
PIN
BMS_485A BMS_485B
GNDX X
Definition
CAN
Rs485
X X X
X X X
When using RS485 protocol, please note that PIN2 must be disconnected.
E Version Manual Required for Changeover Switch
E Version Auto Required for Changeover Switch
Please contact our sales for any compatible contactor purchase requirement .
I Version
E Version
12mm
60mm
E VersionI Version
positive DC
pin contact
nagetive DC
pin contact
cable
clamp contact
nut
male plug
female plug
tight nut
Battery connection diagram
high-voltage lithium battery
CAN/ RS485
Nonpolarized
DC breaker
Power connection
Communication connection
BMSPIN Denition
I N L
I Version
Note: Iport has been wired
during the manufactory.
Note: No need to connect wire
on the X port by enduser!
X N L
E Version
I Version inverter:EPSfunctioncanbeonlybeachievedautomatically.
Do not required for Changeover Switch.
+
-
Battery
E-BAR
PE
N-BAR
RCD
EPS Load
L L
I Version
RCD
Load
RCMB
L
L
N
EPS
AC
EPS breaker: 32A
RCD: type A
wired by manufactor
required for installation
I
I
I Version Auto Do not required for Changeover Switch
+
-
Battery
E-BAR
PE
RCD
EPS Load
L
L
E Version
RCD
Load
RCMB
L
L
N
AC
RCD: type A
wired by manufactor
required for installation
EPS
changeover device( DPDT)
EPS breaker: 32A
PE
+
-
Battery
E-BAR
PE
RCD
EPS Load
L
L
E Version
RCD
Load
RCMB
L
L
N
AC
RCD: type A
wired by manufactor
required for installation
EPS
Contactor Device
Contactor
EPS breaker: 32A
PE
PV2+
PV2 -
PV1+
PV1 -
PV2+
PV2 -
PV1+
PV1 -
PV2+
PV2 -
PV1+
PV1 -
Step4:Insert one Rj45 side of the cable into
BMS port inside of inverter and the other
side into RS485 or Can port of the battery.
B:Communication Connection Steps:
Step1: Disassemble the BMS/Meter
cable gland.
Step2: Prepare a communication
cable(without sheath)and insert
the communication cable through
the cable nut.
Step3:Assemble the cable gland and
screw the cable nut.
The seal is used for waterproof. Please
make sure it has been kept back.
BMS/Meter
BMS/Meter
BMS/Meter
BMS/Meter
EPS
CAN /GEN
LAN /DRM
Gri d
WiF i
RF
BMS/Meter
Upg rade
+
PV1 PV2 BAT
+ +
- - -
ON
OFF
X1-hybrid 3kW-5kW

Other manuals for SolaX Power X1-Hybrid-3.7-D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolaX Power X1-Hybrid-3.7-D and is the answer not in the manual?

SolaX Power X1-Hybrid-3.7-D Specifications

General IconGeneral
BrandSolaX Power
ModelX1-Hybrid-3.7-D
CategoryInverter
LanguageEnglish

Related product manuals