5
z Optional Spec.
Model uM
uTC52 uTC62 uTC72 uTC42 uTC92
Output 2
For heating and cooling control use.
Relay , SSR , 4~20mA , 0~20mA , 0~5V , 0~10V , 1~5V , 2~10V
SPST type SPDT type SPST type SPDT type SPDT type
Alarm 2
3A , 220V , electrical life:100,000 times or more (under rated load)
Available Available Available Available Not
available
SPST type SPST type SPST type SPST type
Alarm 3
3A , 220V , electrical life:100,000 times or more (under rated load)
Display range of heater current : 0.0~99.9A , Accuracy : 1%FS
Included CT : SC-80-T
Heater Break Alarm
(HBA)
Alarm relay : AL1
Available for PV or SV transmission
Transmission
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Remote SV
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Protocol : MODBUS RTU , MODBUS ASCII , TAIE
RS232 , RS485 , TTL
Communication
Baud rate: 2400 , 4800 , 9600 , 19200 , 38400 bps.
Data bits : 8 , Stop bit : 1 or 2bit , Odd or Even parity.
Water/Dust proof
IP65
z Special control output (OUT1)
Model uTC52 uTC62 uTC72 uTC42 uTC92
1φ zero crossing
control(1φSSR)
Available Not available Available Not
available
Available
3φ zero crossing
control(3φSSR)
Not available Available
Motor valve control
Available
1φ phase angle
control(1φSCR)
Not available Available
3φ phase angle
control(3φSCR)
Not available Available
z Programmable RAMP/SOAK
Model uPC52 uPC62 uPC72 uPC42 uPC92
Programmable
RAMP/SOAK
2 patterns with 8 segments each.
The 2 patterns can be linked together as 16 segments use.