MODEL: CVGF500
MODEL NO:
CVGF0500RA0U33809405C1B5C1C23A1A201E3AA0
SERIAL NO: S.O. NO:
ELECTRICAL CHARACTERISTICS:
RATED VOLTAGE: 380 VOLTS 50HZ 3PH
NAMEPLATE NMKW: 338 kW
VOLTAGE UTILIZATION RANGE: 345- 422 VAC
MINIMUM CIRCUIT AMPACITY: 726 AMPS
MAXIMUM FUSE: 1200 AMPS
MAXIMUM CIRCUIT BREAKER 1200 AMPS
MAXIMUM OVERLOAD TRIP: 617 AMPS
MAX MAX
VOLTS-AC HZ PH RLA LRAY
LRAD
COMPRESSOR MOTOR 380 50 3 577 1048 3286
OIL PUMP MOTOR 380 50 31.43 FLA
OIL TANK HEATER 115 50 1000 WATTS TOTAL
CONTROL CIRCUIT 115 50 1500 VA MAX
WHEN MOTOR CONTROLLER PROVIDED BY OTHERS
TRANE ENGINEERING SPEC. S6516-0360 APPLIES
GENERAL CHARACTERISTICS:
REFRIGERANT SYSTEM
TO BE FIELD CHARGED ACTUALLY CHARGED
WITH 340 KG OF R-134A WITH KG OF R-134A
MAXIMUM REFRIGERANT WORKING PRESSURE
HI SIDE 15.2 BAR LOW SIDE 15.2 BAR
FACTORY TEST PRESSURE
HI SIDE 16.7 BAR LOW SIDE 16.7 BAR
FIELD LEAK TEST PRESSURE 82.50 BAR MAX.
TESTED AT BAR
LEAK TEST AND CHARGING SPECIFICATION ARE SUPPLIED
IN CONTROL PANEL (SERVICE LITERATURE MANUAL)
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING
U.S. PATENTS: 4686834 4689967 4715190 5056032
5058031 5434738 5563489 5836382
SERVICE LITERATURE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL:
CVGF-SVN02A-EN AND CVGF-SVU02A-EN
“FOR INSTALLATION REQUIREMENTS, USE ELECTRICAL
CHARACTERISTICS NOT PRODUCT DESCRIPTION”
PRODUCT DESCRIPTION:
MODL CVGF DSEQ A0 NTON 500 VOLT 380
HRTZ 50 CPKW 338 CPIM 940 EVSZ 500
EVBS C EVTB TE25 EFLD WATE EVWB NM15
EVWP 2 EVCO FLGE EVWA RERE CDSZ 500
CDBS C CDTB TE28 CFLD WATE CDWB NM15
CDCO FLGE CDWA RERE ORSZ 23 AGLT UL
SPKGEXPS INSL YES OPTM YES WVUO YES
TRMM TRMS LCLD CLDC LANG ENGL SRTY USTR
SRRL 952 PNCO DISC TEST PTR3
Figure 1. Typical unit nameplate
CVGF-SVN02B-E4
Literature Change History
CVGF-SVX001-E4 (July 2000)
This manual describes the
installation, operation, and
maintenance of CVGF units.
CVGF-SVN02A-E4 (2002)
Replaces CVGF-SVX001-E4.
About this Manual
This manual describes proper
installation of Model CVGF, 50 Hz
and 60 Hz chillers with the Tracer
CH530 Controls platform. See
Figures 2 and 3 for an illustration
of a CVGF Centrifugal Chiller
with the Tracer CH530 Unit
Control Panel.
These chillers are equipped with
microcomputer-based control
systems. A careful review of this
information along with the
submittal package provided for
the unit will assure that the
chiller is correctly installed.
Unit Identification -
Nameplates
When the unit arrives, compare
all nameplate data with order,
submittal and shipping
information. A typical unit
nameplate is shown in Figure 1.
5
General
Information