TDHM AIRFLOW - COOLING
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
CFM
723 713 699 682 661
Watts
58 109 157 204 234
CFM
773 763 747 729 707
Watts
72 125 174 222 256
CFM
823 812 795 776 753
Watts
87 141 182 241 279
CFM
873 861 842 823 798
Watts
103 158 210 260 302
CFM
923 910 892 870 844
Watts
120 177 229 279 325
CFM
998 984 964 940 912
Watts
148 206 258 309 360
CFM
1072 1058 1036 1011 981
Watts
179 238 290 341 396
CFM
1122 1107 1084 1058 1026
CFM
868 856 839 818 794
Watts
101 157 208 258 299
CFM
928 915 896 874 849
Watts
122 179 231 281 327
CFM
988 974 954 931 903
Watts
144 202 254 305 356
CFM
1047 1033 1012 987 958
Watts
169 227 279 330 384
CFM
1107 1092 1070 1044 1013
Watts
195 253 305 356 413
CFM
1197 1181 1157 1128 1095
Watts
237 296 346 395 455
CFM
1287 1269 1243 1213 1177
Watts
284 341 390 436 498
CFM
1347 1329 1301 1269 1232
CFM
1013 999 978 954 926
Watts
154 212 265 315 367
CFM
1082 1068 1048 1020 990
Watts
184 242 294 345 401
CFM
1152 1137 1113 1086 1054
Watts
215 274 325 375 434
CFM
1222 1206 1181 1152 1118
Watts
250 308 358 406 467
CFM
1292 1274 1248 1218 1182
Watts
286 344 392 439 500
CFM
1397 1378 1349 1316 1277
Watts
346 401 446 489 548
CFM
1501 1481 1451 1415 1373
Watts
411 463 503 541 595
CFM
1571 1550 1518 1481 1437
CFM
1157 1142 1118 1091 1058
Watts
218 276 328 377 436
CFM
1237 1220 1195 1166 1131
Watts
257 315 365 413 474
CFM
1317 1299 1272 1241 1204
Watts
300 357 405 450 512
CFM
1397 1378 1349 1316 1277
Watts
346 401 446 489 548
CFM
1476 1456 1426 1392 1350
Watts
395 448 489 529 584
CFM
1596 1575 1542 1504 1460
Watts
474 523 558 591 636
CFM
1716 1693 1658 1617 1569
Watts
560 604 631 726 726
CFM
1796 1771 1735 1693 1642
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
*DHMC100ACV4VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter