MODEL RPM10/RPM20 (-LON)/RPM20-CC PRESSURA
™
ROOM PRESSURE MONITOR
INSTALLATION INSTRUCTIONS
WARNING
The Model RPM10, RPM20 (-LON) and RPM20-CC Room Pressure Monitors must be wired to 24 VAC only.
Wiring the unit to 110 VAC will cause serious damage to the unit and void the warranty.
The pressure sensor must be mounted through the wall between the controlled space (isolation room) and
referenced space (ante room / hallway).
Go to www.tsi.com to download the Operation & Service Manual for the Model RPM10 or RPM20.
These installation instructions guide the installer through the installation of the TSI Model RPM10 PresSura™
Room Pressure Monitor or the TSI Model RPM20 (-LON) / RPM20-CC PresSura Room Pressure Monitor. The
installation instructions cover all monitor versions. Unless specified otherwise, figures and instructions apply
to all versions. Please read these instructions thoroughly before beginning installation.
This product is classified by UL as to fire resistive properties only. See UL File R15545.
Figure 1: Typical Installation
Pressure sensor
with cable
RPM10 Room
Pressure Monitor
RPM20 /
RPM20-LON Room
Pressure Monitor
RPM20-CC Room
Pressure Monitor