Page #1 background image
DV-5a Automatic Water Control Valve Deluge
Electric Actuation Fire Protection Systems
1 1/2 Inch to 8 Inch (DN40 to DN200)
Page 1 of 18 JUNE 2021 TFP1321
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
General
Description
The TYCO DV-5a Automatic Water
Control Valve Deluge Electric Actua-
tion are diaphragm type valves that
can be used in deluge fire protection
systems. When properly trimmed, the
double seat design of the DV-5
a Valve
also provides actuation of fire alarms
upon system operation.
The diaphragm style design of the
DV-5
a Valve allows external resetting,
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5
a features internal and exter-
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5
a in cor-
rosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
The DV-5
a Deluge Electric Actuation
Valve is offered with the DV-5
a Valve
and separately ordered semi-assem-
bled trim as shown in Figure 5.
The DV-5
a Deluge Electric Actua-
tion Valve is offered with or without a
System Main Control Valve.
NOTICE
The DV-5
a Valves described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards of any other authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Available End Connections and Weights — lb/(kg)
End Connection
Nominal Valve Size
ANSI Inches
(DN)
Inlet Outlet
1 1/2
(40)
2
(50)
3
(80)
4
(100)
6
(150)
165,1
mm
8
(200)
Thread Thread
26
(11, 8)
25
(11, 3)
N/A N/A N/A N/A N/A
Groove Groove
25
(11, 3)
25
(11, 3)
60
(27, 2)
95
(43,1)
177
(80,3)
177
(80,3)
327
(148,3)
Flange Groove N/A N/A
66
(30,0)
106
(48,1)
190
(86,2)
N/A
346
(157,0)
Flange Flange N/A N/A
72
(32,7)
116
(52,6)
204
(92,5)
N/A
365
(165,6)

Other manuals for Tyco DN150