PLLD Grounding Clamp Installation Guide P/N 577014-012
2
Kit Contents
Veeder-Root parts required to install the PLLD Transducer grounding clamp are listed in Table 1.
Installation Steps
FAILURE TO FOLLOW THE STEPS BELOW MAY IMPAIR INTRINSIC SAFETY, CAUSE
DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH
1. Before installing this device, turn Off, tag/lock out power to the system, including console and
submersible pumps.
2. A separate 4mm
2
(minimum) wire must be run from the site earth ground to the STP sump in a non-
intrinsically safe conduit or duct (see Figure 1). DO NOT CONNECT THE CLAMP OR BODY OF
THE PLLD PRESSURE SENSOR TO ANY INTRINSCALLY SAFE WIRE THAT CONNECTS TO
THE TLS CONSOLE.
3. Using the ring terminal supplied in the kit, insert the stripped ground wire into the barrel of the ring
terminal.
4. Use a properly sized crimping tool to ensure a good tight bond (see Figure 2).
5. Place the clamp around the sensor and attach the ring terminal to the clamp with the clamp bolt.
6. Securely tighten the clamp bolt until the clamp tightly grips the sensor body and no longer can be
rotated by hand.
7. Confirm continuity between the PLLD sensor body and ground at the electrical panel and between
the electrical panel to the TLS console chassis (reference Figure 3).
Table 1. PLLD Grounding Kit (Part Number 330020-285)
Item Qty. Description P/N
1 1 Clamp grounding 331285-002
2 1 Ring terminal - 1/4”, 12-10 AWG 576048-061
3 1 1/4”-20 x 1.00 “ bolt 514100-407
4 1 1/4”-20 nut hx sst w/lock washer 511000-251
5 1 PLLD Grounding Clamp Installation Guide 577014-012