Humidity Deadband
A deadband widens the setpoint to prevent small changes in humidity from activating humidifiers, compressors and valves
and cause excessive component cycling.
Figure 3.12 below , illustrates humidity control using:
50% setpoint
8% proportional band
2% deadband
Like the proportional band, the deadband is also divided evenly on each side of the setpoint.
0% cooling capacity is required from 49% to 51%.
Below 49%, humidification operates according to the humidity proportional band.
Above 51%, dehumidification operates according to the humidity proportional band.
Figure 3.12 Humidity Control with a Deadband
No. Description
1 ½ of proportional band.
2 ½ of proportional band.
3 Deadband.
3.1.10 Configuring Fan Setpoints
Configures fan-speed control to operate independent of compressor loading (decoupled mode).
1. Touch , then > Setpoints > Fan Control. The FAN CONTROL secondary panel opens.
2. Adjust the setpoint options, then touch Save. The setpoint is updated.
Touch Cancel to discard the changes.
NOTE: Depending on the type of thermal management unit, included components, and control settings of your system,
all of the options listed may not be available on your Vertiv™ Liebert® iCOM™ display.
3 Service Operation
43
Vertiv™ Liebert® iCOM™Installer/User Guide

Table of Contents

Other manuals for Vertiv Liebert iCOM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM and is the answer not in the manual?

Vertiv Liebert iCOM Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM
CategoryControl Unit
LanguageEnglish

Related product manuals