5167798-YTG-J-0218
Johnson Controls Unitary Products 37
Electrical Data
ZF078-150 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps
078
(6)
208 9.8 68 15 2.1 5.2 5.5
None---31.537 40 45
E09 6.8 1 18.9 31.5 37 40 45
E18 13.5 2 37.5 53.4 60.3 60 70
E24 18 2 50 69 75.9 70 80
E36 25.5 2 70.8 95 101.9 100 110
230 9.8 68 15 2.1 5.2 5.5
None---31.537 40 45
E09 9 1 21.7 33.6 40.5 40 45
E18 18 2 43.3 60.6 67.5 70 70
E24 24 2 57.7 78.6 85.5 80 90
E36 34 2 81.8 108.8 115.6 110 125
460 4.9 34 8 1.26 2.6 2.2
None---16.118.320 20
E09 9 1 10.8 16.8 19.5 20 20
E18 18 2 21.7 30.4 33.1 35 35
E24 24 2 28.9 39.4 42.1 40 45
E36 34 2 40.9 54.4 57.1 60 60
575 3.8 28 6 0.66 2 1.8
None---11.913.715 15
E09 9 1 8.7 13.4 15.6 15 20
E18 18 2 17.3 24.1 26.4 25 30
E24 24 2 23.1 31.4 33.6 35 35
E36 34 2 32.7 43.4 45.6 45 50
090
(7.5)
208 13.8 83.1 22 2.1 5.2 5.5
None---40.546 50 50
E09 6.8 1 18.9 40.5 46 50 50
E18 13.5 2 37.5 53.4 60.3 60 70
E24 18 2 50 69 75.9 70 80
E36 25.5 2 70.8 95 101.9 100 110
230 13.8 83.1 22 2.1 5.2 5.5
None---40.546 50 50
E09 9 1 21.7 40.5 46 50 50
E18 18 2 43.3 60.6 67.5 70 70
E24 24 2 57.7 78.6 85.5 80 90
E36 34 2 81.8 108.8 115.6 110 125
460 6.2 41 10 1.26 2.6 2.2
None---19.121.325 25
E09 9 1 10.8 19.1 21.3 25 25
E18 18 2 21.7 30.4 33.1 35 35
E24 24 2 28.9 39.4 42.1 40 45
E36 34 2 40.9 54.4 57.1 60 60
575 4.9 33 8 0.66 2 1.8
None---14.316.115 20
E09 9 1 8.7 14.3 16.1 15 20
E18 18 2 17.3 24.1 26.4 25 30
E24 24 2 23.1 31.4 33.6 35 35
E36 34 2 32.7 43.4 45.6 45 50
102
(8.5)
208 12.2 88 19 3.03 6.8 5.5
None---40.445.950 50
E09 6.8 1 18.9 40.4 45.9 50 50
E18 13.5 2 37.5 55.4 62.3 60 70
E24 18 2 50 71 77.9 80 80
E36 25.5 2 70.8 97 103.9 100 110
230 12.2 88 19 3.03 6.8 5.5
None---40.445.950 50
E09 9 1 21.7 40.4 45.9 50 50
E18 18 2 43.3 62.6 69.5 70 70
E24 24 2 57.7 80.6 87.5 90 90
E36 34 2 81.8 110.8 117.6 125 125
460 5.8 44 9 1.6 3.4 2.2
None---19.721.925 25
E09 9 1 10.8 19.7 21.9 25 25
E18 18 2 21.7 31.4 34.1 35 35
E24 24 2 28.9 40.4 43.1 45 45
E36 34 2 40.9 55.4 58.1 60 60
575 4.4 36 6 1.35 2.4 1.8
None-- - 1516.815 20
E09 9 1 8.7 15 16.8 15 20
E18 18 2 17.3 24.6 26.9 25 30
E24 24 2 23.1 31.9 34.1 35 35
E36 34 2 32.7 43.9 46.1 45 50