445348-YTG-D-0612
2 Johnson Controls Unitary Products
Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
HORIZONTAL SIDEWALL VENTING
For applications where vertical venting is not possible, the only
approved method of horizontal venting is the use of an auxiliary
power vent. Auxilary power venters must be approved by CSA,
UL, or other recognized safety agencies. Follow all application
and installation details provided by the manufacturer of the
power vent.
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Perfor-
mance” table shown represents blower performance WITHOUT
filters.
All applications of these furnaces require the use of field
installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabi-
net. DO NOT attempt to install any filters inside the furnace.
LEFT SIDE
RIGHT SIDE
.5”
.5”
RETURN END
B
24.25”
29.5”
28.5”
Electrical
Entry
Gas Pipe
Entry
Thermostat
Wiring
FRONT
14”
1”
1.5”
23”
SUPPLY END
C
24.38”
20”
.5”
B
Gas Pipe
Entry
Thermostat
Wiring
33”
A
.5”
Electrical
Entry
Vent Connection
Outlet
Vent
Connection
Outlet
4” Diameter
Outlet
Vent Connection
Cabinet and Duct Dimensions
Models
Nominal
CFM (m
3
/min)
Cabinet
Size
Cabinet Dimensions (Inches)
Approximate
Operating Weights
ABC Lbs
TM(8,L)X060A12MP11 1200 A 14 1/2 13 3/8 10.3 94
TM(8,L)X080B12MP11 1200 B 17 1/2 16 3/8 11.8 103
TM(8,L)X080C16MP11 1600 C 21 19 7/8 13.6 114
TM(8,L)X100C16MP11 1600 C 21 19 7/8 13.6 118
TM(8,L)X100C20MP11 2000 C 21 19 7/8 13.6 122
TM(8,L)X120C20MP11 2000 C 21 19 7/8 15.8 129
Ratings & Physical / Electrical Data
Models
Input Output
AFUE
Air Temp.
Rise
Max. Outlet
Air Temp
Blower
Blower
Size
Max
Over-Current
Protect
Total Unit
Amps
Min. wire Size
(awg) @ 75 ft
one way
MBH MBH °F °F HP Amps
TM(8,L)X060A12MP11 60 48 80.0 30-60 160 1/2 6.8 11 x 8 15 9.3 14
TM(8,L)X080B12MP11 80 64 80.0 35-65 165 1/2 6.8 11 x 8 15 9.3 14
TM(8,L)X080C16MP11 80 64 80.0 25-55 155 1/2 6.8 11 x 10 15 9.3 14
TM(8,L)X100C16MP11 100 80 80.0 35-65 165 1/2 6.8 11 x 10 15 9.3 14
TM(8,L)X100C20MP11 100 80 80.0 25-55 155 3/4 8.4 11 x 11 15 10.9 14
TM(8,L)X120C20MP11 120 96 80.0 35-65 165 3/4 8.4 11 x 11 15 10.9 14