Appendix A – CoE Object Dictionary 119
1C33 0 Input sync man-
ager parameter
U8 R Sync manager 3 syn-
chronization settings
-
1 Synchroniza-
tion type
U16 RW 0x00 = Free run (de-
fault)
0x01 = SM sync, SM3
event
0x22 = SM sync, SM2
event
0x02 = DC Sync0
FBA
4 Synchroniza-
tion types sup-
ported
U16 R Drive dependent. Bits:
4…2: 000 = No DC,
001 = DC Sync0
1: SM sync support-
ed
0: Free run support-
ed
-
5 Minimum cycle
time
U32 R See subindex 5 of in-
dex 1C32.
500 000.
-
6 Calc and copy
time
U32 R Delay between the
time of input process
data sampling and the
time when the data is
available for the master
(ns)
88 000.
-
C Cycle time too
small
U16 R See subindex C of in-
dex 1C32.
-
Index SI Name Type Ac-
cess
Information NVS