20. Technical data
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Energizing quantities, rated values and limits
Analog inputs
Table 6. TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity Rated value Nominal range
Current I
r
= 1 or 5 A (0.2-40) × I
r
Operative range (0-100) x I
r
Permissive overload 4 × I
r
cont.
100 × I
r
for 1 s
*)
Burden < 150 mVA at I
r
= 5 A
< 20 mVA at I
r
= 1 A
Ac voltage U
r
= 110 V 0.5–288 V
Operative range (0–340) V
Permissive overload 420 V cont.
450 V 10 s
Burden < 20 mVA at 110 V
Frequency f
r
= 50/60 Hz ± 5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
ABB 29

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Relion 670 series REC670 and is the answer not in the manual?

ABB Relion 670 series REC670 Specifications

General IconGeneral
BrandABB
ModelRelion 670 series REC670
CategoryController
LanguageEnglish

Related product manuals