INTRODUCTION
These
instructions
for
installation
,
operation
and
maintenance
of
VHK
-
R
series
vacuum
circuit
breakers
should
be
read
carefully
and
used
as
a
guide
during
installation
and
initial
operation
.
The
specific
ratings
of
each
model
circuit
breaker
are
listed
on
the
individual
nameplates
.
WARNINGS
WA
1
mm
File
these
instructions
in
a
readily
accessible
place
together
with
drawings
and
descriptive
data
of
the
switchgear
.
These
instruc
-
tions
will
be
a
guide
to
proper
maintenance
of
the
equipment
and
prolong
its
life
and
usefulness
.
Prior
to
any
disassembly
or
insoecticn
of
the
circuit
breaker
,
the
closing
springs
should
be
discharged
,
and
the
breaker
shcuid
be
open
.
Installation
Inspection
RECEIVING
AND
STORAGE
Inspect
the
condition
of
circuit
breaker
vacuum
interrupters
and
electrical
connections
prior
to
installing
the
circuit
breaker
into
the
switchboard
.
Even
though
each
circuit
breaker
is
completely
adjusted
and
tested
at
the
factory
,
shipping
and
handling
condi
-
tions
could
cause
defects
.
Immediately
upon
receipt
of
the
circuit
breakers
,
examine
the
cartons
to
determine
if
any
damage
or
loss
was
sustained
during
transit
.
If
abuse
or
rough
handling
is
evident
,
file
a
damage
claim
at
once
with
the
carrier
and
promptly
notify
the
nearest
District
Office
.
The
company
is
not
responsible
for
damage
of
goods
after
delivery
to
the
carrier
,
however
,
we
will
lend
assistance
if
notified
of
claims
.
Vacuum
Interrupter
Examination
(
See
Fig
.
1
)
f
>
[
-
310
*
»
Unpack
the
circuit
breakers
as
soon
as
possible
after
receipt
.
If
unpacking
is
delayed
,
difficulty
may
be
experienced
in
making
a
claim
for
damages
not
evident
upon
receipt
.
Use
care
in
unpack
-
ing
in
order
to
avoid
damaging
any
of
the
circuit
breaker
parts
.
Check
the
contents
of
each
carton
against
the
packing
list
before
discarding
any
packing
material
.
If
any
shortage
of
material
is
discovered
,
promptly
notify
the
nearest
District
Office
.
Informa
-
tion
specifying
the
purchase
order
number
and
part
numbers
of
the
damaged
or
missing
parts
should
accompany
the
claim
.
:
v
k
grounding
stick
snouid
be
usee
to
ciscnarge
the
mid
-
banc
on
me
vacuum
interrupters
(
1
)
so
sou
ooad
.
before
snv
vc
cone
cr
.
the
interrupters
.
The
insulated
vacuum
envelope
(
2
)
should
be
examined
carefully
for
cracks
in
the
area
of
the
metal
-
to
-
insulation
seals
on
both
ends
and
around
the
mid
-
band
ring
.
Since
a
certain
amount
of
transmitted
light
is
usually
required
to
detect
cracks
,
the
inspec
-
tion
should
be
done
in
a
well
lighted
area
.
If
the
mid
-
band
ring
,
when
so
equipped
,
has
been
bent
by
an
accidental
impact
,
that
area
should
be
specially
scrutinized
for
seal
damage
.
Small
external
chips
will
not
impair
the
useful
life
of
the
interrupter
.
Circuit
breakers
should
be
installed
in
their
permanent
location
as
soon
as
possible
.
If
the
breakers
are
not
to
be
placed
in
service
for
some
time
,
it
is
advisable
to
provide
adequate
means
of
protection
.
This
may
be
done
by
keeping
the
breaker
in
its
original
shipping
carton
and
storing
in
a
warm
,
dry
and
uncontaminated
atmosphere
.
If
the
circuit
breaker
cannot
be
stored
properly
,
it
must
be
thoroughly
checked
before
going
into
service
to
insure
it
has
not
absorbed
moisture
,
rusted
or
become
generally
contami
-
nated
in
any
way
.
Insulation
Structure
All
insulated
parts
should
be
checked
for
damage
.
Any
dust
or
dirt
should
be
removed
by
air
or
wiped
with
a
clean
lintless
cloth
.
The
lead
support
moldings
are
polyester
glass
and
occasionally
have
some
resin
rich
cracks
or
crazing
develop
.
These
do
not
indicate
defective
material
and
should
not
cause
concern
.
CIRCUIT
BREAKER
GENERAL
INFORMATION
Prior
to
initial
installation
of
the
circuit
breaker
into
the
switch
-
board
,
certain
preliminary
inspections
should
be
made
to
insure
proper
operation
.
The
inspection
procedures
for
this
are
given
in
this
section
.
NOTE
:
It
is
recommended
that
a
dielectric
withstand
test
be
made
prior
to
putting
this
or
any
type
vacuum
circuit
breaker
into
service
.
Refer
to
Dielectric
Tests
,
in
the
Maintenance
,
Adjustments
and
Tests
section
of
this
bulletin
,
for
the
correct
test
procedure
.
The
circuit
breaker
is
shipped
with
contacts
closed
,
closing
springs
discharged
and
opening
springs
charged
.
If
the
circuit
breaker
is
furnished
with
an
undervoltage
device
,
the
device