75
6. PERFORMANCE DATA
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC at
those temperatures which are not stated out in the table.
Example:
Model: AWM 10G / ALC 10C
Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Solution:
Overall
Based on the Performance table of AWM 10G / ALC 10C
1. Refer to the Indoor DB column,
- 23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
- 15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C WB
and 17°C WB during 24°C indoor DB is required)
3. Refer to the Outdoor DB column,
- 37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.
1
st
Step
Extrapolation of Indoor WB
Find TC, SC for
(a) Indoor : 24°C DB, 15°C WB
Outdoor : 35°C DB
(b) Indoor : 24°C DB, 15°C WB
Outdoor : 40°C DB
2
nd
Step
Interpolation of Indoor DB
Find TC, SC for
(a) Indoor : 23°C DB, 15°C WB
Outdoor : 35°C DB
(b) Indoor : 23°C DB, 15°C WB
Outdoor : 40°C DB
3
rd
Step
Interpolation of Outdoor DB
Find TC, SC for
(a) Indoor : 23°C DB, 15°C WB
Outdoor : 37°C DB
Downloaded from AC-Manual.com Manuals

Other manuals for Acson AWM 20G

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acson AWM 20G and is the answer not in the manual?

Acson AWM 20G Specifications

General IconGeneral
BrandAcson
ModelAWM 20G
CategoryAir Conditioner
LanguageEnglish

Related product manuals