10 ControlLogix EtherNet/IP Module
Rockwell Automation Publication 1756-IN603C-EN-P - April 2010
To reset the module to its initial out-of-the-box settings, reset the switches to
888 and cycle power.
After cycling power with the switches set to 888, remove the module and set the
switches to their final value. When you set the rotary switches to a value other
than 888, or to the valid IP address values 001…254, the software configuration
determines the IP address.
IMPORTANT
Do not use the 888 switch setting during normal module operation.
Determining the Module IP Address
If BOOTP/DHCP is The module
Enabled Asks for an address from a BOOTP/DHCP server. The server also
assigns other Transport Control Protocol (TCP) parameters.
Not enabled Uses the IP address (along with other TCP configurable parameters)
stored in nonvolatile memory.