6 FLEX I/O Digital Input and Output Modules w/ Diagnostics
Publication 1794-IN096C-EN-P - August 2015
Installing Your Digital Input or Output Module
The input module mounts on a 1794-TB32 or 1794-TB32S terminal base. The output
module mounts on a 1794-TB2, 1794-TB3, or 1794-TB3S terminal base.
1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 2 as
required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left to connect
with the neighboring terminal base/adapter. You cannot install the module
unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they will align
properly with the connector in the terminal base.
Description Description
1 Keyswitch 5 Alignment bar
2 Terminal base 6 Groove
3 Flexbus connector 7 Latching mechanism
4 Module
ATTENTION: During mounting of all devices, be sure that all debris (metal
chips, wire strands, etc.) is kept from falling into the module. Debris that falls
into the module could cause damage on power up.
1
2
3
4
5
6
7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Flex I/O and is the answer not in the manual?

Allen-Bradley Flex I/O Specifications

General IconGeneral
BrandAllen-Bradley
ModelFlex I/O
CategoryAdapter
LanguageEnglish

Related product manuals