20 /
INSTALLATION
Fitting the Coaxial Flue
(Ø 60 / 100 Vertical)
Note: See table for maximum and minimum ue runs.
Contents:
1x Conical Adaptor (60/100mm)
1x Vertical Flue Kit (80/125mm)
The vertical ue kit is supplied with a specially designed
weather proof terminal tted, it can be used either with a at
roof or a pitched roof.
The Vertical ue kits useable lengths with the pitched roof
ashings are indicated in Fig. 7.
Before proceeding to t the ue, ensure that the maximum ue
length has not been exceeded (See the tables) and that all
elbows and bends have been taken into consideration, for each
additional 90° elbow 1 metre must be subtracted from the total
ue length, and for each 45° 0.5 metres must be subtracted from
the total ue length (the height of the vertical adaptor and a 45°
bend can be seen in Fig. 8).
Mark the position of the ue hole in the ceiling and/or roof (see
Fig. 7 for distance from wall to the centre of the ue).
Cut a 130mm diameter hole through the ceiling and/or roof and
t the ashing plate to the roof.
DO NOT cut the vertical ue kit.
To connect the vertical ue kit directly to the boiler, place the
vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust
manifold and secure with the clamp, t the vertical adaptor onto
the vertical starter kit (note: there is no need to use a clamp to
secure this as it is a push t connection), the vertical ue kit must
then be inserted through the roof ashing, this will ensure that
the correct clearance above the roof is provided as the terminal
is a xed height.
Should extensions be required, they are available in 1 metre
(Part No. 3318077), 500mm (Part No. 3318078) and they must be
connected directly to the vertical starter kit before connecting
the adaptor to allow the vertical ue kit to be tted. In the event
that extension pieces need to be shortened, they must only be
cut at the male end and it must be ensured that the inner and
outer ue remain ush.
When utilising the vertical ue system, action must be taken
to ensure that the ue is supported adequately to prevent the
weight being transferred to the appliance ue connection by
using 1 ue bracket per extension.
When the ue passes through a ceiling or wooden oor, there
must be an air gap of 25mm between any part of the ue
system and any combustible material. The use of a ceiling
plate will facilitate this. Also when the ue passes from one
room to another a re stop must be tted to prevent the passage
of smoke or
re, irrespective of the structural material through
which the ue passes.
180 mm
Vert Adaptor
(supplied with ue kit)
Vertical Starter
Part No: 3318079
* This length will vary
according to the type
of ashing installed
Total length
of Vertical Kit
1355 mm
Useable length
of Vertical ue
690 mm*
Fig. 7
Fig. 8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ariston ALTEAS ONE Net Series and is the answer not in the manual?

Ariston ALTEAS ONE Net Series Specifications

General IconGeneral
BrandAriston
ModelALTEAS ONE Net Series
CategoryBoiler
LanguageEnglish

Related product manuals