Notice:
Above mentioned power supply cord is the cables which connect air on-off of indoor to
indoor/outdoor unit. Power supply cord of indoor/outdoor unit is the power supply cable
connecting indoor and outdoor unit
The section area of power supply cord core is minimized one. To avoid voltage pressure
dropped down, while longer power supply cord needed, the section area should be enlarged for
one gauge.
The connection wires to indoor unit is the cable of 27IEC53(RVV) type, 300/500V; while the
connection wires to outdoor unit and the connection wires from outdoor to indoor unit is the
multi-end of cable (neoprene)of 245IEC57(YZW)type,300/500V. if the single core with double skin
type of cable is chosen for installation,, please choose 1# gauge of section area and wrapped with
special jacket for electrician.
All of the ceiling/floor type unit is without accessorial electric heating
Commissioning
The system should be power on for 8 hours for preheat before the first time startup.
During winter, while after 8 hours power off, the performance test should be 2 and half hours
power on later:
◇ Power on the system and start up, r cooling mode.
◇ After 3 minutes compressor protection, check whether there is normal cooling air come from
indoor unit and if there is abnormal noise come from indoor/outdoor units
◇ Configure the mode with “fan” and check whether there is high air come from indoor unit.
◇ Operate “swing” mode, check whether the louver is properly swaying.
◇ Press the other buttons on the remote controller and check whether the complete unit is on
proper working condition
◇ Keep on running for 1 hour with “cooling” mode and check if the drainage system is on proper
condition