5 Installation BECKHOFF Drive Technology
32 Version 6.2 AX5000
5 Installation
Caution - Risk of injury through electric shock!
De-energise all electrical components (servo drive, control cabinet, etc.)
before commencing the installation or deinstallation.
5.1 Mechanical installation
Attention
Destruction of the servo drive!
• Always install the servo drive vertically.
• Provide adequate ventilation for the servo drive. The permissible ambient
conditions are specified in the "Technical data" section.
• It is essential to adhere to the required distances (see diagrams below).
5.1.1 Installation in the control
cabinet
Caution - Risk of injury through electric shock!
The mounting plate must be earthed according to the statutory regulations.
Attention
Connection of the protective earth conductor on the AX5000:
The servo drives AX5000 have earthing bolts on the device housing. To
attach the protective earth conductor via the earthing bolts, use at least the
cross section that is applied to the wide voltage input “X01” (PE).