Product overview
KL1xxx 17Version: 1.0.0
2-channel digital input terminal 24V
DC
, type 3
The KL1402 and KL1412 supplement the proven KL1404, KL1414, KL1408 und KL1418 digital input
terminals with their type-3 specification. The current/voltage characteristics have been optimized for 2-wire
sensors. The input current in low state is increased to a minimum value of 1.5mA and therefore supports the
majority of commercially available 2-wire sensors. A typical value for the energy-saving high current is
2.2mA. The input complies with the EN 61131-2 type 3 standard and is compatible with type 1.
2.4.1 KL1402, KL1412 – Technical data
Technical data KL1402, KS1402 KL1412, KS1412
Connection technology 4-wire
Number of inputs 2
Nominal voltage 24V
DC
(-15%/+20%)
Signal voltage ‘0’ -3V to +5V (EN 61131-2, type 1/3)
Signal voltage ‘1’ 11V to 30V (EN 61131-2, type 3)
Signal current “0” 0 to 1.5mA
Signal current "1" 2.0 to 2.5mA
Input filter typically 3.0ms typically 0.2ms
Current consumption from K-bus typically 3mA
Current consumption power
contacts
typ. 1mA + load
Electrical isolation 500V (K-bus / field voltage)
Bit width in process image 2 inputs
Configuration no address or configuration settings required
Weight approx. 50g
Permissible ambient temperature
during operation
0°C ... +55°C
Permissible ambient temperature
during storage
-25°C ... +85°C
Permissible relative humidity 95%, no condensation
Vibration / shock resistance according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity [}35]
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Installation position variable
Protection class IP20
Pluggable wiring for all KSxxxx terminals
Approvals
CE, cULus, ATEX [}40], GL