Functions when operated on MP-Bus
Connection on the MP-Bus Network topology
1235
MP
+
~
–
T
U
Y
A)
A) more actuators and sensors
(max.8)
There are no restrictions for the
network topology (star, ring, tree or
mixed forms are permitted).
Supply and communication in one
and the same 3-wire cable
• no shielding or twisting necessary
• no terminating resistors required
Connection of active sensors Connection of external switching contact
1235
MP
+
~
–
T
U
Y
A)
A) more actuators and sensors
(max.8)
• Supply AC/DC 24 V
• Output signal DC 0...10 V
(max. DC 0...32 V)
• Resolution 30 mV
1235
MP
+
~
–
T
U
Y
A)
p
A) more actuators and sensors
(max.8)
• Switching current 16 mA @ 24 V
• Start point of the operating range
must be parameterised on the MP
actuator as ≥ 0.5 V
Functions for actuators with specific parameters (Configuration necessary)
Override control and limiting with AC 24 V with relay contacts Override control and limiting with DC 24 V with relay contacts
T
~
abd
U
T
~
Y
e
5123
ab
Close
max
Open
Y
Y (DC 0 ... 10 V)
e.g. 1N 4007
+
ab
U
T
~
Y
e
5123
ab
Close
max
Y
Y (DC 0 ... 10 V)
-
Control 3-point
ab
~
T
U
e.g. 1N 4007
1235
YU
Position control: 90° = 100s
Flow control: Vmax = 100s
EP..F+MP
Electr. 2-way PI-CCV EPIV, Flange, PN 16