Faults
77
Greenstar FS/Combi FS – 6 720 810 590 (2020/04)
17.3 Faults that are not shown on the display
Table 41 Faults not shown on the display
Appliance faults Elimination
Combustion noise too loud; rumbling noises Insert code plug correctly; replace if defective.
Check gas type.
Check inlet gas pressure; adjust if defective.
Check flue gas system; clean or repair if defective.
Check gas/air ratio in the combustion air and flue gas; replace gas valve if defective.
Flow noises Set pump speed correctly to match maximum output.
Set pump mode.
Heating-up takes too long Set pump speed correctly to match maximum output.
Set pump mode.
Flue gas readings incorrect; CO levels too high Check gas type.
Check inlet gas pressure; adjust if defective.
Check flue gas system; clean or repair if defective.
Check gas/air ratio in flue gas; replace gas valve if defective.
Violent ignition, poor ignition Check gas type.
Check inlet gas pressure; adjust if defective.
Check power supply.
Check electrodes for visual damage; replace if defective.
Check flue gas system; clean or repair if defective.
Check gas/air ratio; replace gas valve if defective.
Check gas valve; replace if defective.
Check burner; replace if required.
DHW has unpleasant odor or has a dark color Perform thermal disinfection of the DHW circuit.
Replace sacrificial anode in the tank (if installed).
Consult local water department.
Set supply temperature (e.g. of the FW200 control)
exceeded
Switch off automatic anti-cycle timer, i.e., set value to 0.
Set the required anti-cycle timer, e.g. default setting of 3 minutes.
Condensate in air box Insert diaphragm in the mixer unit per installation instructions; replace if defective.
DHW temperature is not reached (combi boilerKWB..-3A
only)
Insert code plug correctly; replace if defective.
Check whether voltage (120 VAC) is present between terminal 1 and terminal 3; repair
if defective.
Check turbine; replace if defective.
Heatronic is flashing (i.e. all buttons, all display segments,
burner indicator etc. are flashing)
Replace fuse Si 3 (24 V) (6.3 A fuse according to IEC default).