Briggs & Stratton Power Products Home Generator System
Owners Manual
Problem
Cause
Correction
Engine is running, but no
AC output is available.
1. Generator circuit breaker is open.
2. Fault in generator.
3. Poor wiring connections or defective
transfer switch.
4. Circuit breaker open or defective.
1. Reset circuit breaker.
2. Contact Briggs & Stratton service
facility.
3. Check and repair.
4. Reset or replace circuit breaker.
Engine runs good at no-
load but “bogs down"
when loads are
connected.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
1. Disconnect shorted electrical load.
2. See “Essential Circuits” on page 7.
3. Contact Briggs & Stratton service
facility.
Engine will not start; or
starts and runs rough.
1. 15 Amp fuse missing or blown.
2. Dirty air cleaner.
3. Out of fuel.
4. Spark plug wire not connected to
spark plug.
5. Bad spark plug.
6. Intake valve stuck open or closed.
7. Engine compression lost.
8. Failed battery.
1. Install (new) 15 Amp fuse.
2. Clean or replace air cleaner.
3. Open fuel valve(s); check propane tank.
4. Connect wire to spark plug.
5. Replace spark plug.
6. Contact Briggs & Stratton service
facility.
7. Contact Briggs & Stratton service
facility.
8. Replace battery.
Engine shuts down during
operation.
1. Out of fuel.
2. Fault indicator blinking.
1. Check fuel valves, fill propane tank.
2. Count blinks and refer to “Fault
Detection System” on page 16.
Engine lacks power.
1. Dirty air filter.
2. Generator overloaded
1. Replace air filter.
2. See “Essential Circuits” on page 7.
Loss of power on
essential circuits.
1. Feeder circuit breaker at load center
open.
2. Generator circuit breaker is open.
3. Transfer switch stuck in Open
position.
1. Reset circuit breaker.
2. Reset circuit breaker.
3. Remove 15A fuse from generator
control panel, wait 30 seconds and
replace fuse.
TROUBLESHOOTING
www.mymowerparts.com
Briggs & Stratton Generac Generator Discount Parts Call 606-678-9623 or 606-561-4983

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Briggs & Stratton Generac and is the answer not in the manual?

Briggs & Stratton Generac Specifications

General IconGeneral
BrandBriggs & Stratton
ModelGenerac
CategoryPortable Generator
LanguageEnglish

Related product manuals