ELECTRICAL DATA
U N I T S I Z E ---
VOLTAGE,
SERIES
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE
{
MIN
WIRE
SIZE
{
MAX
LENGTH
(FT)
}
MAX
LENGTH
(FT)
}
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
18---30
208/230/1 253 187
41 9.0 0.5 11.70 14 14 166 158 20
24---30 54 11.3 0.8 14.80 14 14 131 125 25
30---30 72.5 14.8 0.8 19.20 12 12 161 154 30
36---30 88 17.0 0.9 22.10 12 12 140 133 35
42---30 104 21.2 0.9 27.40 10 10 181 172 40
48---30 137 21.2 1.2 27.60 10 10 179 170 40
60---30 148 28.9 1.2 37.30 8 8 207 197 60
30---50
208/230/3 253 197
63 10.4 0.75 13.75 14 14 66 63 20
36---50 77 11.3 0.9 15.03 12 12 96 92 25
42---50 88 13.4 0.9 17.65 12 12 82 78 25
48---50 91 13.78 1.2 18.43 10 10 125 119 30
60---50 123 18.7 1.2 24.58 8 10 146 89 35
36---60
460/3 506 414
39 5.5 0.5 7.38 14 14 247 235 15
42---60 44 6.4 0.5 8.50 14 14 214 203 15
48---60 46 7.1 0.6 9.41 14 14 193 184 15
60---60 62 8.6 0.6 11.35 14 14 160 152 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30° C(86° F) , consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60° C (140° F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than un coated ( no---plated), 60
or 75° C (140 or 167° C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 A WG) is used, consult applicable tables
of th e NEC (ANSI/NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i me --- D e l a y f u se .
F L A --- Fu l l L o a d Am p s
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
A--WEIGHTED SOUND LEVEL (dBA)
UNIT SIZE --- VOLTAGE, SERIES
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18---30 75 52 59.5 64.5 71 67 61.5 54.5
24---30 76 52.5 63.5 69.5 72 67.5 64.5 59.5
30---30, 50 76 52 64 70 71 68 66.5 65
36---30, 50, 60 76 53 69 66.5 69.5 66.5 63.5 62
42---30, 50, 60 76 57 65 68 72.5 67.5 64 59
48---30, 50, 60 76 57.5 65 68 70.5 69 64 60.5
60---30, 50, 60 77 61 62.5 70 72.5 70 67 60
A--WEIGHTED SOUND LEVEL (dBA) WITH SOUND HOOD
UNIT SIZE --- VOLTAGE, SERIES
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18---30 74 52.0 59.5 64.0 68.0 64.0 60.0 52.5
24---30 75 53.5 63.0 69.0 70.5 66.5 64.0 58.5
30---30, 50 75 53.0 64.5 69.5 70.5 67.5 64.5 60.5
36---30, 50, 60 75 54.0 68.5 65.5 68.0 65.0 62.0 57.5
42---30, 50, 60 76 58.0 64.5 67.0 71.0 65.5 61.0 54.5
48---30, 50, 60 75 58.0 64.0 68.0 69.0 65.5 60.5 55.5
60---30, 50, 60 75 59.5 61.5 67.5 70.0 68.0 64.0 57.5
CHARGING SUBCOOLING (TXV --TYPE EXPANSION DEVI CE)
UNIT SIZE--- VOLTAGE, SERIES REQUIRED SUBCOOLING (_F)
18---30 11
24---30 11
30---30, 50 9
36---30, 50, 60 11
42---30, 50, 60 13
48---30, 50, 60 13
60---30, 50, 60 11
25HBR3