DIAGNOSIS AND SOLUTION (CONT)
Outdoor DC Fan Motor (DC motor that controls the chip on the PCB)
1. Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the fan motor is faulty and
must be replaced. Otherwise, proceed to step 2.
2. Power on the unit and when the unit is in standby, measure the pin4-5 voltage in the feedback signal connector. If the value is not 5V, change the
PCB. Otherwise, proceed to step 3.
3. Rotate the fan by hand, measure the pin1-5, pin 2-5 and pin 3-5 voltage levels in the feedback signal connector. If any voltage is not in the
positive voltage fluctuation, the fan motor is faulty and must be replaced.
Fig. 39 — Outdoor DC Fan Motor (DC motor that controls the chip on the PCB)
NO.12345
Color Orange Grey White Pink Black
Signal Hu Hv Hw Vcc GND
Color Red Blue Yellow
Signal W V U