Installing the UPC Open
UPC Open Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Integration Guide All rights reserved
7
Wiring the UPC Open to the CCN network
The UPC Open's CCN Port communicates using EIA RS-485 and supports 9600 bps. Future versions will support
baud rates of 19.2 and 38.4 kbps.
NOTES
The UPC Open is intended to be wired directly to one piece of Carrier equipment.
NOTE The exception is a Multiple Chiller application, which consists of 2 or 3 chillers configured for
Lead/Lag, with a potential third chiller as a standby chiller. In this application, wire the CCN network between
the UPC Open and chillers in a daisy-chain configuration. All other applications have one network segment
between the UPC Open and the interfaced Carrier equipment.
Refer to the CCN Installation and Start-up Guide for more details on wiring the CCN bus.
Multiple chiller application only (Lead/Lag, and, possibly, a standby chiller)
Single unit application
Wiring specifications for CCN
Cable:
20 AWG, general purpose, 3-conductor, foil shielded copper wire
Maximum length:
1000 f