Specifications
5-5
Overcurrent Protection
Table 5-5
Overcurrent Protection Per Model
UPS Model Input Protection
R3000 XR-NA Circuit protector for each load segment
R3000j XR-JPN Circuit protector for each load segment
R3000h XR-NA Circuit protector for each load segment
R3000h XR-JPN Circuit protector for each load segment
R3000e XR-INT Circuit protector for each load segment
R3000i XR-EURO Circuit protector for each load segment
R3000i XR-SCHUKO Circuit protector for each load segment
R3000i XR-SA Circuit protector for each load segment
Battery Specifications
Table 5-6
Battery Specifications
Feature Specification
Type Sealed lead-acid; maintenance-free
Voltage 120V battery string
Charging 24 hours to full charge
4 hours to 90% capacity at default nominal utility voltage and no load
Battery Runtime
Table 5-7
Estimated Battery Runtime
Load
(Percent)
Estimated Battery Runtime
(Minutes)
UPS with ERM
Runtime (Minutes)
20 40 120
50 12 45
80 6.5 30
100 5 20