EasyManuals Logo
Home>DAB>Switch>ESC plus 4T

DAB ESC plus 4T User Manual

DAB ESC plus 4T
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
ENGLISH
8
5.2.4: to restore ESC plus factory settings, press the three status keys (++) at the same time until
the display shows the flashing number 88. After that switch off the device and power up it again to
start a new calibration phase.
ATTENTION!: this operation doesn't reset any error condition on ESC plus.
6 TABLE OF IDENTIFICATION OF ERRORS:
TROUBLE MEANING POSSIBLE CAUSE POSSIBLE REMEDY
6.1: the motor does not
start and the ESC plus
display the frequency.
Self-diagnosis 3.2.1. Supply voltage is too low. Check.
6.2: ESC plus powers
the motor for a fraction
of a second.
Self-diagnosis 3.2.1. High voltage drop at
breakaway.
Increase the cross section of the
supply cables.
6.3: display of SB
blinking.
Operating dry or at low
load.
Stand-by for restoring of
level (10, 22, 45, 90
minutes).
- No water in the well.
- Pump unsuitable for the
motor.
- Reverse rotation of the
motor.
Check.
ATTENTION: the load should always
be considered as live.
6.4: display of UL and
the motor is off.
Final lack of water
(after at least 4 tests and
167 minutes).
As above. Solve the problem and reset ESC
plus by switching it off and then
power up on again (see 3.2.13).
6.5: display of flashing
OL and the motor is off.
Too high absorption of
current detected.
Pause pending return to
level (10, 20, 40 min).
Incorrect adjustment.
- Overload.
- Pump clogged with sand.
- Power supply voltage too
high.
- Pump unsuitable.
- Problems on motor.
Check correct current absorption and
current threshold setting (AM).
(Arbitrarily increasing the adjustment
setting is not a solution).
See following points.
Solve the problem and reset ESC
plus by switching it off and then on
again (see 3.2.13).
6.6: display of
permanent OL and the
motor is off.
Too high absorption of
current detected.
Overload alarm.
- The motor does not start.
- Overload.
- Pump silted up.
- Supply voltage too high.
- Unsuitable pump.
- Problems with the motor.
6.7: display of OF. Missing phase. - Missing phase.
- The motor is not
connected.
Solve the problem and reset ESC
plus by switching it off and then on
again (see 3.2.13).
6.8: the ESC plus is not
activated.
- No jumper on SW
contacts.
- The external contact is
open/disconnected.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DAB ESC plus 4T and is the answer not in the manual?

DAB ESC plus 4T Specifications

General IconGeneral
BrandDAB
ModelESC plus 4T
CategorySwitch
LanguageEnglish

Related product manuals