16
Dehumidification Mode
Air Discharge Direction(only remocon operation)
The air discharge direction procedure is below.
Fixed Up/Down Fixed
Up/Down
Auto Mode
(1) When the room temperature is higher than 28°C (Cooling Mode)
!Compressor and lndoor Fan
@ The fan will automatically operate as following Figure
!Desired temperature < Room temperature
Outdoor Fan, Compressor : ON
Indoor Fan : Low speed
@ Desired temperature ≥ Room temperature
Compressor : 3 min/ON, 5 min/OFF
Indoor Fan : 3 min 30 second/ON, 4 min 30 second/OFF
Fan Speed : low speed
# Room temperature ≤ 18°C
Compressor : OFF
Indoor Fan : 1 min/ON, 7 min/OFF
Fan speed : Low speed