8 | Charging refrigerant
Installer reference guide
46
2MXM40+50A
R32 Split series
4P600463-4E – 2021.12
8.7 To fix the fluorinated greenhouse gases label
1 Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total refrigerant charge
expressed as tonnes CO
2
equivalent.
f GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes: GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.

Table of Contents

Other manuals for Daikin 2MXM50A2V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXM50A2V1B and is the answer not in the manual?

Daikin 2MXM50A2V1B Specifications

General IconGeneral
BrandDaikin
Model2MXM50A2V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals