EasyManuals Logo
Home>Daikin>Air conditioning>4MKD90BVM

Daikin 4MKD90BVM User Manual

Daikin 4MKD90BVM
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #203 background imageLoading...
Page #203 background image
Troubleshooting Si12-411A
192 Service Diagnosis
5.18 CT or Related Abnormality
Remote
Controller
Display
H8
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
1
Method of
Malfunction
Detection
A CT or related error is detected by checking the compressor running frequency and CT-
detected input current.
Malfunction
Decision
Conditions
The compressor running frequency is below 55 Hz and the CT input is below 0.1 V.
(The input current is also below 1.25 A.)
If this error repeats 4 times, the system will be shut down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Power transistor defective
Internal wiring broken or in poor contact
Reactor defective
Outdoor unit PCB defective

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MKD90BVM and is the answer not in the manual?

Daikin 4MKD90BVM Specifications

General IconGeneral
BrandDaikin
Model4MKD90BVM
CategoryAir conditioning
LanguageEnglish

Related product manuals