3 | Specific installer safety instructions
Installer reference guide
16
2MXM68+3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1C – 2020.08
3 Specific installer safety instructions
Always observe the following safety instructions and regulations.
Unit installation (see
"6Unit installation"[
4
25]
)
WARNING
Installation shall be done by an installer, the choice of materials and installation shall
comply with the applicable legislation. In Europe, EN378 is the applicable standard.
Installation site (see
"6.1Preparing the installation site"[
4
25]
)
CAUTION
Check if the installation location can support the unit's weight. Poor installation is
hazardous. It can also cause vibrations or unusual operating noise.
Provide sufficient service space.
Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may
cause vibrations.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
Opening the unit (see
"6.2Opening the unit"[
4
29]
)
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF BURNING/SCALDING
DANGER: RISK OF ELECTROCUTION
Connecting the refrigerant piping (see
"7.2Connecting the refrigerant
piping"[
4
36]
)
CAUTION
No brazing or welding on site for units with R32 refrigerant charge during
shipment.
During installation of the refrigeration system, joining of parts with at least one
part charged shall be performed taking into account the following requirements:
ð inside occupied spaces non permanent joints are not allowed for R32 refrigerant
except for site made joints directly connecting the indoor unit to piping. Site
made joints directly connecting piping to indoor units shall be of non permanent
type.
CAUTION
Do NOT connect the embedded branch piping and the outdoor unit when only
carrying out piping work without connecting the indoor unit in order to add another
indoor unit later.

Table of Contents

Other manuals for Daikin 4MXM80N2V1B9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXM80N2V1B9 and is the answer not in the manual?

Daikin 4MXM80N2V1B9 Specifications

General IconGeneral
BrandDaikin
Model4MXM80N2V1B9
CategoryAir Conditioner
LanguageEnglish

Related product manuals