• Outdoor Unit • AZQS-BV1
2
• Split - Sky Air • AZQS-BV1
6
2 Specifications
Notes
(1) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A
and ≤ 75A per phase.
(2) Short-circuit power
(3) RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
(4) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(5) See separate drawings for electrical data
(6) Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents
produced by equipment connected to public low-voltage systems with input current \>16A and ≤ 75A per phase
(7) PED unit category: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
2-5 Electrical Specifications AZQS71BV1 AZQS100BV1 AZQS125BV1 AZQS140BV1
Power supply Name V1
Phase 1~
Frequency Hz 50
Voltage V 220-240
Voltage range Min. % -10
Max. % 10
Current Nominal running
current (RLA)
Cooling A 16.20 -
Zmax List Complies to EN6100-3-
3
Complies to EN61000-3-12
Recommended fuses A 20 32
Current - 50Hz Maximum fuse amps (MFA) A 20 -
Current - 60Hz Maximum fuse amps (MFA) A -
Wiring connections For power supply Remark - See installation manual outdoor unit
For connection with
indoor
Remark - See installation manual outdoor unit
Power supply intake Outdoor unit only