Indoor Unit Control (RA Models) SiBE18-821_C
100 Function
7. Indoor Unit Control (RA Models)
7.1 Temperature Control
Definitions of
Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
The illustration is for wall mounted type as representative.
Temperature
Control
The temperature of the room is detected by the room temperature thermistor. However, there is
difference between the “temperature detected by room temperature thermistor” and the
“temperature of lower part of the room”, depending on the type of the indoor unit or installation
condition. Practically, the temperature control is done by the “target temperature appropriately
adjusted for the indoor unit” and the “temperature detected by room temperature thermistor”.
Target temperature
Set temperature
Room temperature
Room thermistor temperature
(R12321)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FTXG25EV1BW and is the answer not in the manual?

Daikin Super Multi Plus E-Series FTXG25EV1BW Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FTXG25EV1BW
CategoryAir Conditioner
LanguageEnglish

Related product manuals