AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016 7
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
SW = 1.1x
1 2 3 4 5
HACCP
Actual temperature measurement for the HACCP function h01
Last registered peak temperature h10
Selection of function and sensor for the HACCP function. 0 = no HACCP function. 1 = S4
used (maybe also S3). 2 = S5 used
h11 0 2 0
Alarm limit for the HACCP function h12 -50.0°C 50.0°C 8.0°C
Time delay for the HACCP alarm h13 0 min. 240 min. 30 min.
Select signal for the HACCP function. S4% (100% = S4, 0% = S3) h14 0% 100% 100%
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01-t06 0 hours 23 hours 0 hours
Six start times for defrost.
Setting of minutes.
0=OFF
t11-t16 0 min 59 min 0 min
Clock - Setting of hours *** t07 0 hours 23 hours 0 hours
Clock - Setting of minute *** t08 0 min 59 min 0 min
Clock - Setting of date *** t45 1 31 1
Clock - Setting of month *** t46 1 12 1
Clock - Setting of year *** t47 0 99 0
Miscellaneous
Delay of output signals after start-up o01 0 s 600 s 5 s
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation
7=change reference (activate r40). 8=alarm function when closed. 9=alarm function
when open. 10=case cleaning (pulse signal).
o02 1 10 0
Network address o03 0 240 0
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
o04 OFF ON OFF
Access code 1 (all settings) o05 0 100 0
Readout of Software version o06
Display step = 0.5 (normal 0.1 at Pt sensor) o15 no yes no
Max hold time after coordinated defrost o16 0 min 60 min 20
Select signal for display view. S4% (100%=S4, 0%=S3) o17 0% 100% 100%
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation
7=change reference (activate r40). 8=alarm function when closed. 9=alarm function
when open. 10=case cleaning (pulse signal).
o37 0 10 0
Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI-
function, when DI is selected to door function or to door alarm
o38 1 3 1
Activation of light relay (only if o38=2) o39 OFF ON OFF
Rail heat On time during day operations o41 0% 100% 100
Rail heat On time during night operations o42 0% 100% 100
Rail heat period time (On time + Off time) o43 6 min 60 min 10 min
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off. *** o46 0 2 0
Selection of EL diagram. See overview page 2 * o61* 1 5 1
Download a set of predetermined settings. See overview previous page. * o62* 0 3 0
Access code 2 (partly access) *** o64 0 100 0
Save the controllers present settings to the programming key. Select your own number. o65 0 25 0
Load a set of settings from the programming key (previously saved via o65 function) o66* 0 25 0
Replace the controllers factory settings with the present settings o67 OFF On OFF
Service
Status codes are shown on page 5 S0-S32
Temperature measured with S5 sensor *** u09
Status on DI1 input. on/1=closed u10
Temperature measured with S3 sensor *** u12
Status on night operation (on or off) 1=closed *** u13
Temperature measured with S4 sensor *** u16
Thermostat temperature u17
Read the present regulation reference u28
Status on DI2 output. on/1=closed u37
Temperature shown on display u56
Measured temperature for alarm thermostat u57
Status on relay for cooling ** u58
Status on relay for fan ** u59
Status on relay for defrost ** u60
Status on relay for railheat ** u61
Status on relay for alarm ** u62
Status on relay for light ** u63
Status on relay for compressor 2 ** u67
Status on relay for compressor fan ** u71