EasyManuals Logo
Home>Danfoss>Timer>103E7

Danfoss 103E7 Installation Guide

Danfoss 103E7
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
GB
Danfoss Heating
5
3. Fix the wallplate and terminal block to the wall, or plaster box, as
required. Ensure that the screw heads do not protrude beyond
the vertical centre rib of the wallplate, or this will prevent the
module correctly locating onto the wallplate.
4. Surface cables can only enter from below the unit. Cut an
appropriate cable aperture in the wiring cover. If the wallplate is
mounted on a plaster box, cables can enter from the rear below
the terminal block.
5. Electrical connections are simpli ed by using a Wiring Centre.
However, if this is not used, the wallplate terminal identi cation
is as shown.
If the system being controlled is 230 Vac, then terminals 3 and L
must be linked with insulated cable capable of carrying full load
current. Whilst the unit does not require an earth connection,
a terminal is provided on the wallplate for earth continuity
purposes.
6. Refer to the wiring diagrams on page 6-9, connect the unit as
shown.
Screw  xing holes
(screwheads MUST NOT
protrude above centre rib)
Vertical
centre rib
Wallplate & Terminals
Load Mains Supply (via 3 amp fuse)
ON SPARE COM N L
123 5 6

Other manuals for Danfoss 103E7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 103E7 and is the answer not in the manual?

Danfoss 103E7 Specifications

General IconGeneral
BrandDanfoss
Model103E7
CategoryTimer
LanguageEnglish

Related product manuals